RH Systems 973-SF6 Analyzer

RH Systems Model 973-SF6 Analyzer

For measurement of humidity and SF6 purity in gas insulated switchgear systems

The RH Systems Model 973-SF6 Analyzer is expertly designed to measure humidity and SF6 purity in gas-insulated switchgear systems. This advanced analyzer presents humidity measurement data in ppmv, ppmw, and dew/frost point, available at either system pressure or standard pressure. Purity measurement is directly displayed as % volume SF6. Both humidity and purity measurements utilize precise and reliable condensation techniques, ensuring accurate and dependable results.


Advanced Gas Recovery System

The RH Systems 973-SF6 Analyzer is equipped with a sophisticated gas recovery system that securely stores the sampled gas during the measurement process in its internal storage tank. Once the measurement is complete, the stored gas can be efficiently pumped back into the original compartment or transferred to another container. This feature not only conserves gas but also minimizes environmental impact. Additionally, the system records starting and ending pressures, providing a comprehensive overview for effective gas management. This ensures that the integrity of the gas is maintained throughout the process, promoting safety and operational efficiency. With its robust design and cutting-edge technology, the RH Systems 973-SF6 Analyzer stands as a vital tool for maintaining the optimal performance of gas-insulated switchgear systems.


RH Systems 973-SF6 Analyzer

Easy, Automated Usage

User configurable via the full color active matrix LCD touch screen, the 973-SF6 may be configured for measurement of humidity, % volume SF6, or both, with either automatic or manually initiated pump back. Using the bi-directional RS-232 communications port, all measurement data may be easily transferred into a PC for electronic storage and report generation.

Verifiable Calibration

Easily check the calibration at any time using the built-in Ice Test function which provides instant verification of system accuracy and integrity.

Connect and Go

The system is supplied ready for immediate use complete with industry standard quick connect fittings and sampling tube.

RH Systems 973-SF6 Analyzer

RH Systems 973-SF6 Analyzer

RH Systems 973-SF6 Analyzer Specification

Measuring range:
Frost/Dew Point-55 …+20°C at atmospheric pressure
Humidity content by volume20 …20,000 ppmv
Humidity content by weight2.5 …2500 ppmw
% Volume SF680 …100%
Pressure1.25 …10 bar abs.

Accuracy:
Frost/Dew point±0.5°C
ppmv/ppmw±6% of reading
% Volume SF6±0.5%
Pressure± 3 kPa (± 0.4 PSIA)

Reproducibility:
Frost/Dew Point± 0.2°C
% Volume SF6± 0.3%
Pressure0.1% FS
Thermoelectric Mirror cooling:3-stage
Cooling:Air
Display:Active Matrix Color Graphic LCD
Digital I/O:RS-232
Gas couplings:Quick connect fitting
Mirror temperature sensor:PRT-100
Sample gas pressure:1 …30 bar
Sample gas flow rate:0.5 …1 l/min
Operation temperature:-10 …+40°C
Storage temperature:-20 …+50°C
Ambient humidity:90% RH max., non condensing in operation
Voltage:100…240 VAC, 50/60 Hz
Power consumption:200 Watt
Width:440 mm (490 mm with transport case)
Height:155 mm (360 mm with transport case
Depth:410 mm (650 mm with transport case)
Weight:15 kg (27 kg with transport case)



Our Services

Training

Empowering Through

Knowledge and Skills

Repair

Expert Technicians for

Optical Performance

Calibration

Ensuring Accuracy and Compliance

Sales

Unparalleled Precision Equipment and Solutions


Our Vendor Partners

Subscribe to Our Newsletter

 Stay in touch with us today.

Thank You For Your Feedback

Our team will message you back as soon as possible.
In the meantime we invite you to visit our website.